Battery Input Data | |
Battery Type | Lead Acid or Lithium Ion |
Battery Voltage Range (V) | 40-60 |
Maximum Charging Current (A) | 280 |
Maximum Discharge Current (A) | 280 |
Charging Strategy for Li-ion Battery | Self-adaptation to BMS |
Number of Battery Inputs | 1 |
PV Input Data (String) | |
Maximum PV Access Power (W) | 30000 |
Maximum DC Input Power (W) | 24000 |
Maximum DC Input Voltage (V) | 800 |
Starting Voltage (V) | 160 |
MPPT Voltage Range (V) | 160-650 |
Nominal DC Input Voltage (V) | 550 |
Maximum PV Input Current (A) | 36+36 |
Maximum Input Short Circuit Current (A) | 54+54 |
No. of MPPT Trackers / Strings per MPPT Tracker | 2/2+2 |
AC Input/Output Data | |
Nominal Active Power AC Input/Output (W) | 15000 |
Maximum Apparent Power AC Input/Output (VA) | 16500 |
Rated AC Input/Output Current (A) | 22.8/21.8 |
Maximum AC Input/Output Current (A) | 25/24 |
Maximum Continuous Current AC (mains load) (A) | 70 |
Peak Power (off-grid) (W) | 2 times rated power, 10s |
Power Factor Regulation Range | 0.8 early to 0.8 late |
Nominal Input/Output Voltage and Range (V) | 220/380V, 230/400V 0.85Un-1.1Un |
Nominal Input/Output Frequency and Range (Hz) | 50/45-55, 60/55-65 |
Network Connection Form | 3L+N+PE |
Total Harmonic Distortion Current (THDi) | <3% (of nominal power) |
DC Component of the Network | <0.5% In |
Efficiency | |
Maximum Efficiency | 97.6% |
Euro Efficiency | 97.0% |
MPPT Efficiency | >99% |
Equipment Protection | |
Integrated Protections | DC reverse polarity protection, AC output overcurrent protection, Thermal protection, AC output overvoltage protection, AC short circuit protection, DC component monitoring, Overload protection, Earth fault current monitoring, Arc circuit breaker (optional), Grid monitoring, Islanding protection, DC terminal insulation impedance monitoring, Residual current detection (RCD), Overvoltage protection level |
Overvoltage Protection Level | TYPE II (DC), TYPE II (AC) |
Interface | |
Communication Interface | RS485/RS232/CAN |
Tracking Mode | GPRS/WIFI/Bluetooth/4G/LAN (optional) |
General Data | |
Operating Temperature Range (℃) | -40 to +60℃, >45℃ Derating |
Permissible Ambient Humidity | 0-100% |
Permitted Altitude | 3000 m |
Noise | ≤60dB |
Degree of Protection (IP) | IP 65 |
Inverter Topology | Not Isolated |
Category Overvoltage | OVC II (DC), OVC III (AC) |
Cabinet Size (WxHxD mm) | 456×750×268.5 (Excluding Connectors and Brackets) |
Weight (kg) | 50.6 |
Cooling Type | Intelligent Air Cooling |
Warranty | 5 Years/10 Years (Depends on installation location, see warranty policy) |
Network Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |