Specifically designed to respond to very small movements, this version is suitable for use in offices, schools, and the workplace in general. The lens has been developed to achieve two zones of different sensitivity: The overall area of 8 x 8 meters is sensitive to normal movement whereas the central section of 4 x 4 meters is able to respond to “body presence” by detecting very small movements.
Double terminals
Double terminals for the easy “looping” between multiple 18 Series. The Max. wire size for each terminal is 2.5 mm2. The terminals are equipped with a test hole to take a test probe.
Settings
The ambient light intervention threshold can be set from the lowest value (about 1 lx) to the optimal value for offices and working area (about 500 lx), with the possibility to exclude to-tally the intervention of the light sensor (set to ∞ lx). The light on time following last detection can be regulated between 12 seconds to 35 minutes.
Features
- Sensing area up to 64 m2: movement 8x8 m, presence 4x4 m.
- Two sensing areas: “presence” suitable for zones of low activity, and “movement” suitable for transit areas or zones of high activity.
- Supply voltage: 110...230 V AC (50/60Hz).
- Ambient light intervention threshold: 4 lx...500 lx.
- Light on time after last detection from 12 seconds to 35 minutes.
- 1 NO contact 10 A, with “zero crossing” switching.
- Wall mounting compatible with 60 mm box and 2 or 3 module box. For internal installation.
- Reduced installation time thanks to the connection of cables with push-in terminals.
- Split terminals for connecting other products in parallel.
- Double terminals for easy “looping” in and out.
- Modern design.
- Number of contacts: 1 NO (SPST-NO)
- Rated current/Maximum peak current (A): 10/20 (100 A - 5 ms)
- Rated voltage/Maximum switching voltage (V AC): 250/400
- Rated load AC1 (VA): 2500
- Rated load AC15 (VA): 450
- Standard contact material: AgSnO2
- Rated power AC/DC VA (50 Hz)/W: 1.5/1
- Operating range V AC (50/60 Hz): 96...253
- Electrical life at rated load AC1 (cycles): 100 - 10
- Ambient light intervention threshold (lx): 4...500
- Light ON time after last detection: 12 s...35 min
- Ambient temperature range: -10°C .... +50°C
- Protection category: IP40
Nominal lamp rating 230 V
- Incandescent/halogen (W): 1000
- Fluorescent lamp with electronic ballast (W): 500
- Fluorescent lamp with electromagnetic ballast (W): 350
- CFL (W): 300
- LED 230 V (W): 300
- Halogen or LV LED with electronic ballast (W): 300
- Halogen or LV LED with electromagnetic ballast (W): 500